Anti-islanding and Distributed Generation System

Main Article Content

Meraj Alam

Abstract

This paper proposes an anti-islanding control for a grid connected distributed generation system. The proposed control is based on d-q frame. The scheme using current command reference as positive feedback is utilized to drift the PCC voltage beyond the threshold limits to detect islanding within 2 seconds as prescribed by IEEE 1547. The test system configuration and parameters for anti-islanding study is prepared on IEEE 929 standards. The effectiveness of proposed anti-islanding scheme is validated by simulation done in MATLAB platform.